This range complements selected articles
Stromwandler mit Kabeldurchführung für den Schienenaufbau ab Lager lieferbar
Die mit einem robustem Scharnier trennbaren Wandler lassen sich einfach in bestehende Installationen einbauen. Das spart Zeit und Geld, weil keine Leiter getrennt werden müssen
Kabelumbau-Wandler bis 18 mm Durchmesser
Kabelumbau-Wandler bis 28 mm Durchmesser
Kabelumbau-Wandler bis 42 mm Durchmesser
Stromwandler von Janitza - Höchste Qualität für beste Messergebnisse
UMG 96RM-E-CH mit 90...277 V AC, 90...250 V DC
Blue Week Promotion 2024 (25. Nov. – 01. Dec.)
Product description
The innovative UMG 96 RM-E energy measurement device monitors and measures residual currents (RCM - Residual Current Monitor) and currents at the ZEP (Central Earthing Point). The UMG 96RM-E multifunctional network analyzer can be used for monitoring and checking electrical parameters in power distribution systems or for continuous monitoring of residual currents
Main features:
UMG 96RM-E energy measurement device with Ethernet and RCM
(UL)Supply voltage 90V..277V (50/60Hz); 90V..250V DC
300V CATIII Voltage measurement
Measurement category 300V CATIII
3 voltage measurement inputs (L-N: 20V-300V; L-L: 34V- 520V; 45Hz-65Hz)
3+1 current measurement inputs 0..5A
Response current 5mA
Measurement in three-phase 4-conductor systems with earthed neutral conductor up to max. 277V / 480V
Measurement in unearthed three-phase 3-conductor systems up to max. 480V
Measurement in single-phase 3-conductor systems up to max. 220V-440V
Measurement in single-phase 2-wire systems up to max. 220V
2 digital outputs3 digital inputs/outputs, configurable
2 analog inputs, optionally also as temperature or residual current measurement input (RCM)
Clock and data memory (256 MB flash)
Interfaces: Ethernet, RS485
Protocol: TCP/IP, Modbus RTU
Communication:
Modbus (RTU, TCP, Gateway)
TCP/IP
HTTP (freely configurable homepage)
FTP (file transfer)
SNMP
NTP (time synchronization)
SMTP (e-mail function)
DHCP
SNTP
TFTP
BACnet (optional)
Interfaces:
RS485
Ethernet
Measuring accuracy:
Work: Class 0.5 (... / 5 A)
Current: 0.2 %
Voltage: 0.2 %
Voltage quality:
Harmonics up to the 40th harmonic
Rotating field components
Distortion factor THD-U / THD-I
Networks:
TN, TT, IT networks
3- and 4-phase networks
Up to 4 single-phase networks
Measurement data memory:
256 MByte Flash
Temperature measurement input:
- PT100, PT1000, KTY83, KTY84
2 digital outputs:
Pulse output kWh / kvarh
Switching output
Limit value output
Logic output
Remote via Modbus / Profibus
3 digital inputs / outputs:
Optional inputs or outputs
2 analog inputs:
Analog, temperature or residual current input (RCM)
Grid visualization software:
Free GridVis Essentials