B.92057204

ATiCS2CH-63A-ISO 400V

Automatisches Umschalt- und Überwachungsgerät
Schweizer Standardausführung gemäss
NIN Kap.7.10 (ergänzend zu Kap.1-6) & EN 61439

Product description

The ATICS®-...-ISO series of changeover and monitoring devices includes all functions for switching between two independent supply lines and for monitoring unearthed power supplies. The integration of the power section and the electronics in a flat, compact device reduces the space required in the control cabinet, minimizes the wiring effort and reduces the possibility of faults. For maximum reliability, ATICS® has been consistently developed in accordance with functional safety guidelines (SIL 2).

Plug connectors on all connecting cables - in conjunction with the optional bypass switch - enable uninterrupted testing of the ATICS®. In the event of servicing, replacement is therefore possible without interrupting the power supply. ATICS® thus increases the level of safety, particularly in intensive care units and operating theaters.


Is used for Used for sensitive systems, such as those in Group 2 medical areas, require a safe and reliable power supply even in the event of a fault. Redundant supply lines and the design of the supply network as an (unearthed) IT system make a major contribution to a safe power supply.


Features and functions:

- Perfect for space-saving installation / retrofitting

- Compact device for easy installation of safety power supplies with functional safety in accordance with DIN EN 61508 (SIL 2), e.g. for Group 2 medical areas in accordance with DIN VDE 0100-710 (VDE 0100-710) / IEC 60364-7-710

- Increased safety and availability by integrating changeover and IT system monitoring in one compact device

- All-in-one: integration of switch-disconnector and control unit

- Solutions for every application

- Convenient installation and commissioning

- For sensitive systems in Group 2 medical areas

- Insulation monitoring included in the scope of functions

- Saves time and money

- Safe in operation

- Robust switch-disconnector contacts

- Mechanical interlock

- Manual operation directly on the device

- Functional safety SIL 2

- Certified by TÜV SÜD in accordance with EN 61508 (VDE 0803) SIL 2 and DIN VDE 0100-710 (VDE 0100-710)

-Uninterruptible maintenance

- Plug-in connections and optional bypass switch

- Excellent communication and parameterization capability


Technical features:

- Overvoltage category: III

- Special firmware suitable for Swiss applications

- Rated operating voltage Ue: 230V (AC 160...276V)

- Supply voltage Us: from monitored mains

- Communication via RS485 / BMS bus for native integration into existing BMS bus structures

- Mains voltage Un (operating range): AC400V

- Frequency range fn: 48...62Hz

- Insulation monitoring: Measuring range: 10 kΩ...1 MΩ

- Response value Ran1 (ALARM 1) 50...500 kΩ

- Load current monitoring (IT system transformer)

- Measuring range IL (TRMS): 10...110% of the response value

- Response value adjustable: 5...(50) 100 A (1 A steps)

- incl. measuring current transformers STW2 and STW3.

- Mains connection monitoring

- Connection monitoring of PE

- Self-monitoring with automatic message

- Temperature monitoring (IT system transformer)

- PTC thermistor according to DIN 44081 max. 6 in series

- Output: 1 potential-free changeover contact

- Dimensions B234x H263 x D73.5mm

- Functional safety according to SIL 2

- Monitoring for short circuit at the output


Installation position:

According to the technical device manual: Display-oriented = horizontal