iso685-S-P+FP200 - Erdschlussüberwachungsgerät für AC/DC

Hauptstromkreisen (IT-Systemen) AC 0…690 V oder DC 0…1000 V

Product description

The ISOMETER iso685 is an insulation monitoring device for IT systems in accordance with IEC 61557-8. It can be used universally in AC, 3(N)AC, AC/DC and DC systems. In AC systems, extensive DC-fed system components may also be present (e.g. power converters, inverters, controlled drives).


Device variants:


iso685-D:

The iso685-D device version has a high-resolution, graphical LC display and controls for direct operation of the device functions

Operating elements for direct operation of the device functions.


iso685-S:

The iso685-S device version has no display and no operating unit. It can be used in

Used in combination with FP200 and is operated indirectly via this.

Parameterization can also be carried out via the web browser or a COM465.


Option "W"

The device variants are optionally available with the W option for extreme climatic and mechanical

mechanical stresses.


Main features:

- Predefined measurement profiles

- Reliable measurement of insulation resistance, voltage, capacitance and frequency

- Integrated web server

- Modbus TCP/RTU

- Insulation fault location


Features and functions:

iso685-...-P

- ISOMETER® for IT AC voltage systems with galvanically connected rectifiers or converters and for IT DC voltage systems (IT = unearthed systems)

- Automatic adaptation to the existing system leakage capacitance

- Combination of and further profile-dependent measuring methods

- Two separately adjustable response value ranges from 1 kΩ...10 MΩ

- Connection monitoring (monitoring of the measuring cables)

- High-resolution graphic LC display

- Graphical representation of the insulation curve over time (isoGraph)

- Automatic dimming of the display (submarine mode)

- Automatic device self-test

- History memory with real-time clock (3-day buffer) for storing a maximum of 1023 alarm messages with date and time

- Current or voltage output 0(4)...20 mA, 0...400 μA, 0...10 V, 2...10 V (galvanically isolated) analogous to the measured insulation value of the system

- Freely programmable digital inputs and outputs

- Ethernet interface with BCOM, Modbus TCP/RTU and HTTP protocol

- RS-485/BS (Bender sensor bus) for data exchange with other Bender components with Modbus RTU protocol

- Remote setting via the Internet or Intranet (web server/option: COMTRAXX® Gateway)

- Remote diagnostics via the Internet (only by Bender Service)

- ISOnet: Internal separation of the ISOMETER® from the IT system to be monitored (e.g. when several IT systems are linked)

- ISOnet priority: Permanent priority of a device in the network

- ISOloop: Special function for ring networks (all networks are linked).

- isoData: permanent uninterrupted data transmission

- Generation of locating currents for selective insulation fault location

- Display of insulation faults selectively localized by EDS systems

- Parameterization of EDS systems

- EDSsync: Synchronous distribution of EDS trigger information in coupled systems

- Customer-specific texts for each measuring channel

EDS44x

- Insulation fault location in AC, 3AC and DC IT systems

- Up to 12 W, WR and WS series measuring current transformers can be connected

- Insulation fault location sensitivity: EDS440 2...10 mA, EDS441 0.2...1 mA

- Response sensitivity residual current measurement: EDS440 100 mA...10 A, EDS441 100 mA...1 A

- Communication of the components via BS bus (RS-485) or BB bus


Technical features:

- For coupled IT systems and with display for front panel mounting FP200

- Supply voltage Us: AC 100...240 V - DC 120...240 V

- Frequency range Us: 50 Hz, 60 Hz

- Monitored IT system:

- Nominal mains voltage Un: AC 0...690 V (0...600 V UL)

- Nominal mains voltage Un: DC 0...1000 V (0...600 V UL)

- Response value Ran1 (Alarm 1): 1 kΩ...10 MΩ (10 kΩ)

- Response value Ran2 (alarm 2): 1 kΩ...10 MΩ (40 kΩ)

- Graphic display, 127 x 127 pixels, 40 mm x 40 mm

- Digital inputs: 3 / Digital outputs: 2

- Analog output: 1

- Interfaces: Ethernet TCP/IP/http / RS-485 / BMS

- Dimensions: (Wx Hx D) 107.5mm x 100mm x 110mm


Applications:

- AC, DC or AC/DC main circuits

- AC/DC main circuits with directly connected direct current components such as power converters, inverters, controlled drives

- UPS systems, battery networks

- Heaters with phase angle control

- Systems with switching power supplies

- IT systems with high leakage capacitances

- Systems with insulation fault location