B.98110019

CTAC120 Wandler Typ A 120 mm

für RCM420 RCMS460/490 EDS440/460/490

Product description

The CTAC series measuring current transformers are highly sensitive measuring current transformers that convert AC currents into an evaluable measurement signal in conjunction with RCM or RCMS series residual current monitoring and evaluation devices.


They are also suitable for use in insulation fault location systems for IT systems (EDS). They are used to record the locating current generated by a PGH or ISOMETER IRDH locating current generator. The locating current is converted into an evaluable measurement signal in conjunction with insulation fault locators from the EDS series. The connection to the respective devices is made via a two-wire cable.


Device features:

- Rated voltage 800 V

- Overvoltage category III

- Rated current I

- CTAC120 at IΔn ≥ 100 mA 330 A

- Dimensions HxWxD: 211x188x66 mm

- Inner diameter: 120 mm


Application CTAC... measuring current transformer

Connection to an RCMS series residual current monitoring system, RCM series residual current monitoring device or EDS series insulation fault location system


Application CTAC.../01 measuring current transformers:

Connection to an insulation fault locator EDS473(E)-12, EDS474(E)-12, EDS461, EDS491 or EDS441

Read more