B.74043002

RCMA420CH-D-2 Differenzstrom Überwachungsgerät

Allstromsensitiv, für TN und TT Netze
Schweizer Standardausführung gemäss
NIN Kap.5.3.2.3

Product description

The RCMA420 AC/DC sensitive residual current monitoring device is used to monitor earthed systems (TN and TT systems) in which DC residual currents or residual currents can occur whose magnitude is permanently greater than zero. These are in particular loads with six-pulse bridge rectifiers or half-wave rectification with smoothing, e.g. converters, chargers, construction machinery with frequency-controlled drives. Currents in individual conductors can also be monitored with the RCMA420.


The pre-warning level (50...100 % of the set response value IΔn2) allows a distinction to be made between pre-warning and alarm. As the measured value is recorded via measuring current transformers, the device is virtually independent of the nominal voltage and current of the system.


Features and functions:

- All-current sensitive residual current monitoring device type B according to IEC 62020 and IEC 60755

- RMS value measurement (AC + DC)

- Two separately adjustable response values 10...500 mA

- Frequency range 0...2000 Hz

- Start-up, response and release delay adjustable

- Digital measured value display via LC display

- Measured value memory for trigger value

- Connection monitoring measuring current transformer

- Indicator LEDs for operation, alarm 1, alarm 2

- Internal/external test/reset button

- Two separate alarm relays with 1 changeover contact each

- Working/quiescent current and fault memory selectable

- Permanent self-monitoring

- Multifunctional LC display

- Password protection for device settings

- Sealable transparent cover

- 2-module housing (36 mm)

- RoHS-compliant

- Spring terminal (two terminals per connection)


Technical features:

- Version with spring terminals

- Classification according to IEC 60755 - Type B

- Mains form: TN / TT systems

- Special firmware suitable for Swiss applications

- Supply voltage: 70 - 300 VAC/DC

- Measuring channels 1

- Residual currents AC + pulsating DC

- Rated frequency 0 ... 2000 Hz

- Response value I n1: 50 ... 100 %

- Response value I n2: 10 mA ... 600mA

- Alarm relay main message: 1 changeover contact

- Alarm relay pre-warning: 1 changeover contact

- Designed for W20AB ..., W35AB ..., W60AB series transformers

- Dimensions: W 36 x H 90 x D 70.5 mm


Applications:

All-current sensitive residual current monitoring in earthed 2-, 3- or 4-wire systems (TN and TT systems)

Monitoring of regulated drives, UPS systems, construction machines, printing machines, battery systems, laboratory equipment, woodworking machines, MF welding systems, furniture industry, medical systems, etc.

All-current sensitive current monitoring of normally de-energized individual conductors (e.g. N-conductors)


Installation position:

According to the technical device manual: Display-oriented = horizontal

Read more
Downloadcenter
Shop
Contact