Fail-safe operation of systems

Fail-safe operation of systems

With the LINETRAXX® RCMS150 series
In most cases, insulation faults in TN systems lead to the electrical system being switched off. To prevent this, it is important to detect deteriorating measured values or faults quickly. With all-current sensitive Residual current monitoring devices, this is possible right down to the final circuit. For this reason, the solution is particularly suitable for systems that have to be operated with high must be operated with high availability.

LINETRAXX® RCMS150 series

  • Alternative to iso-testing in accordance with DGUV V3
  • All-current sensitive measured value acquisition type B
  • Pure DC fault evaluation
  • Can be used in the smallest of spaces
  • RS-485 with Modbus RTU or BMS
  • Data can be visualized

The six-channel residual current monitoring devices RCMS150... are designed for measuring DC and AC residual currents in earthed power supplies. These can be caused by insulation faults on loads. Residual currents up to a level of = 500 mA in a frequency range of DC...2 kHz can be measured.

They are suitable for applications with a load current of up to 32 A and are therefore particularly suitable for monitoring final circuits. Two separately adjustable response values allow a distinction to be made between pre-warning and alarm.


LINETRAXX® devices have an RS-485 interface with either BMS protocol or Modbus RTU. Measured and alarm values are transmitted via this interface and parameterization is also possible.


Individual parameterization must always be adapted to the system and operating conditions on site. This is the only way to meet the requirements of the standards.


Please observe the limits of the application range specified in the technical data.

Features

  • Permanent residual current monitoring
  • All-current sensitive residual current monitoring device type B with 6 channels K1...6 (each channel offers 2 measuring channels: 1 x RMS, 1 x DC)
  • Ideal for space-sensitive applications
  • Easy installation on top-hat rail or screw mounting on installation distribution board
  • 2 separately adjustable response values (RMS or DC) per channel
  • Permanent self-monitoring
  • Fully shielded measuring current transformers to prevent interference from disturbing magnetic fields
  • Compatible with Bender gateways of type COM465IP, CP9..
  • RCMS150 (RS-485 interface with BMS protocol)
    - Compatible with RCMS460/490 in the system network
    - Address range 2...90, can be set directly on the device
    - Up to 89 RCMS150s can be used on the bus
  • RCMS150-01 (RS-485 interface with Modbus RTU protocol)
    - Compatible in the system network with other Modbus RTU-capable device series from Bender, including the RCMB300 series and RCMB13...-01
    - Address range 1...99 can be set directly on the device using a snap-in potentiometer
    - Address range 1...247 can be set via the bus
    - Up to 247 RCMS150-01 can be used on the bus

Application

Our RCMS150 series is suitable for measuring direct and alternating currents up to = 500 mA in a frequency range of DC 0...2 kHz. The monitored circuit is rated with a voltage of 300 V and a load current of 32 A. The device can be used up to 2000 m above sea level.