Product description

The UMG 806 energy meter offers the right solution for different requirements. The powerful basic device is ideally suited for cost-oriented applications and is equipped with Modbus RTU. Among other things, it offers the option of measuring and recording residual currents. By continuously monitoring the residual current, dangerous fault currents can be detected at an early stage and system damage, including production downtime, can be avoided. The UMG 806 can be expanded with three modules: the Ethernet communication module, the analog input module and the digital input module.

Another advantage is the compact design of the measuring device and modules. This makes optimum use of the already limited space in the control cabinet.


Functions and features:

4 voltage / 4 current channels via current transformer 1/5 A

Residual current measurement

Temperature input

Pulse output

Modbus-RTU onboard

Modbus-TCP - per module

 SNMP V2c - per module


Power quality measurement:

Harmonics up to the 31st harmonic

Internal 4 MB data memory


Technical features:

Nominal voltage 80...270 V AC/DC

Power consumption max. 7 VA

Display with backlight

90 mm × 90 mm × 63.5 mm

Protection class IP20


Voltage measurement:

230 VLN / 400 VLL (+/-10%) acc. to IEC

400 VL-L (+/-10%) acc. to IEC

Sampling frequency 8 kHz / phase


Current measurement (../1A) (../5A):

Rated current 5A

4 channels

Measuring range 0.005 ... 6 Arms


Interface:

RS485 interface 2-wire

Modbus-RTU protocol

Transmission rate up to 38.4 kbps


Functional note:

With module EI1 compatible with RCM 202-AB, for retrofitting type A and type B measurement


Application note:

Ideal for top-hat rail applications in data centers and industry