This range complements selected articles
Stromwandler mit Kabeldurchführung für den Schienenaufbau ab Lager lieferbar
Die mit einem robustem Scharnier trennbaren Wandler lassen sich einfach in bestehende Installationen einbauen. Das spart Zeit und Geld, weil keine Leiter getrennt werden müssen
Kabelumbau-Wandler bis 18 mm Durchmesser
Kabelumbau-Wandler bis 28 mm Durchmesser
Kabelumbau-Wandler bis 42 mm Durchmesser
UMG 96-PA-CH 24...90 V AC, 24...90 V DC
Product description
3-in-1 energy management: | power quality monitoring | RCM monitoring.
The UMG 96-PA energy measurement device can combine four functions in one device and can be modularly extended by two analog inputs - either as 0-20 mA analog inputs (e.g. DC measurement) or as RCM measurement inputs with cable break detection and additional temperature measurement:
Energy management system
- Continuous energy monitoring
- Identification of potential savings
- Reduction of energy costs
- Compliance with tax & regulatory requirements
Power quality
- Secure, highly available power supply
- Avoidance of production downtimes
- Maximize uptime / preventive maintenance
- Avoidance of quality defects in the product
Residual current monitoring (RCM)
- Permanent monitoring of residual currents
- Supports fire and personal protection
- Reduced effort for the DGUV V3 test
- Higher system availability
General:
- Measuring accuracy for voltage, current 0.2%
- Measuring accuracy for active energy (kWh, .../5 A) class 0.2S
Supply voltage:
- AC 90 V - 277 V (50/60) Hz or DC 90 V - 250 V, 300 V CAT III
Inputs and outputs:
- 3 digital inputs and outputs each
- 1 analog output
RMS value measurement - instantaneous values, e.g:
- Current, voltage, frequency
- Active, reactive and apparent power
- Power factor
Energy measurement:
- Active, reactive and apparent energy
- Tariffs: HT / NT
Ambient conditions:
- Temperature range, operation: K55 (-10 ... +55 °C)
Acquisition of average values, e.g:
- Voltage, current / current and maximum
- Active, reactive and apparent power / current and maximum
- Frequency / current and maximum
Measurement of voltage quality:
- Harmonics per order / current and voltage: 1.-40.
- Distortion factor THD-U /THD-I in %
- Current and voltage, zero, positive and negative sequence
Measurement data recording:
- 4 MB memory (flash)
- Average, minimum, maximum values
Interface / protocol:
- RS485 / Modbus RTU
Programming / limit values / alarm management:
- Comparator (2 groups with 3 comparators each)
Grid visualization software
- Free GridVis Essentials
Optional additional functions with the GridVis Standard and Expert packages
Measurement voltage input (3 x):
- Overvoltage category: 600 V CAT III
- Measuring range, voltage L-N, AC (without transformer): 0 ... 600 Vrms (± 10%)
- Measuring range, voltage L-L, AC (without transformer): 0 ... 1040 Vrms (± 10%)
- Frequency measuring range: 45 ... 65 Hz
- Sampling frequency per channel (50 / 60 Hz): 8.33 kHz
- Measurement in quadrants: 4
- Networks: TN, TT
Measuring current input (3 x):
- Rated current: 1 / 5 A
- Overvoltage category: 300 V CAT II
- Sampling frequency: 8.33 kHz
Mechanical properties:
- Protection class according to EN 60529 (with seal = IP54): Front IP40 / Rear IP20
- Mounting according to IEC EN 60999-1 / DIN EN 50022: Front panel
Installation:
Built-in device, 96 x 96 x 86 mm (WxHxD)
Supply voltage: 24-90 V AC / 24-90 V DC
Installation category: 300 V CAT III
Accessories (included):
-Installation instructions
-Safety instructions included
-Mounting kit
-RS485 terminating resistor 120 Ohm
Observe installation position and minimum distances according to installation instructions:
- Top/bottom 50mm distance
- Lateral distance 20mm