This range complements selected articles

Current transformer RX

Stromwandler mit Kabeldurchführung für den Schienenaufbau ab Lager lieferbar

Current transformer Disconnectable RX

Die mit einem robustem Scharnier trennbaren Wandler lassen sich einfach in bestehende Installationen einbauen. Das spart Zeit und Geld, weil keine Leiter getrennt werden müssen

Isolating current transformer KUW-1

Kabelumbau-Wandler bis 18 mm Durchmesser


Isolating current transformer KUW-2

Kabelumbau-Wandler bis 28 mm Durchmesser


Isolating current transformer KUW-4

Kabelumbau-Wandler bis 42 mm Durchmesser


Janitza current transformer

Stromwandler von Janitza - Höchste Qualität für beste Messergebnisse


This week only at a special price - And off to the shopping cart!
OP.52.32.001-KIT

UMG 96-PA-CH 90...277 V AC, 90...250 V DC

4 MB Speicher, Modulares Energiemessgerät
Including Ethernet module
Blue Week Promotion 2024 (16. Dec. – 22. Dec.)

Product description

3-in-1 energy management: | power quality monitoring | RCM monitoring.

The UMG 96-PA energy measurement device can combine four functions in one device and can be modularly extended by two analog inputs - either as 0-20 mA analog inputs (e.g. DC measurement) or as RCM measurement inputs with cable break detection and additional temperature measurement:


Energy management system

- Continuous energy monitoring

- Identification of potential savings

- Reduction of energy costs

- Compliance with tax and regulatory requirements


Power quality

- Secure, highly available power supply

- Avoidance of production downtime

- Maximize uptime / preventive maintenance

- Avoidance of quality defects in the product


Residual current monitoring (RCM)

- Permanent monitoring of residual currents

- Supports fire and personal protection

- Reduced effort for DGUV V3 testing

- Increased system availability


General:

Measuring accuracy for voltage, current 0.2%

 Measuring accuracy for active energy (kWh, .../5 A) class 0.2S


Supply voltage:

AC 90 V - 277 V (50/60) Hz or DC 90 V - 250 V, 300 V CAT III


Inputs and outputs:

3 digital inputs and outputs each

1 analog output


RMS value measurement - instantaneous values, e.g:

Current, voltage, frequency

Active, reactive and apparent power

Power factor


Energy measurement:

Active, reactive and apparent energy

Tariffs: HT / NT


Ambient conditions:

Temperature range, operation: K55 (-10 ... +55 °C)


Acquisition of average values, e.g:

Voltage, current / current and maximum

Active, reactive and apparent power / current and maximum

Frequency / current and maximum


Measurement of the voltage quality:

Harmonics per order / current and voltage: 1.-40.

Distortion factor THD-U /THD-I in %

Current and voltage, zero, positive and negative sequence


Measurement data recording:

4 MB memory (flash)

Average, minimum and maximum values


Interface / protocol:

RS485 / Modbus RTU


Programming / limit values / alarm management:

Comparator (2 groups with 3 comparators each)


Grid visualization software

Free GridVis Essentials

Optional additional functions with the GridVis Standard and Expert packages


Measurement voltage input (3 x):

Overvoltage category: 600 V CAT III

Measuring range, voltage L-N, AC (without transformer): 0 ... 600 Vrms (± 10%)

 Measuring range, voltage L-L, AC (without transformer): 0 ... 1040 Vrms (± 10%)

Frequency measuring range: 45 ... 65 Hz

Sampling frequency per channel (50 / 60 Hz): 8.33 kHz

Measurement in quadrants: 4

Networks: TN, TT


Measuring current input (3 x):

Rated current: 1 / 5 A

Overvoltage category: 300 V CAT II

Sampling frequency: 8.33 kHz


Mechanical properties:

Protection class according to EN 60529 (with seal = IP54): Front IP40 / Rear IP20

Mounting according to IEC EN 60999-1 / DIN EN 50022: Front panel


Installation:

Built-in device, 96 x 96 x 86 mm (WxHxD)

Supply voltage: 90 - 277 V AC

Installation category: 300 V CAT III


Accessories (included):

Installation instructions

Safety instructions included

Mounting kit

RS485 terminating resistor 120 Ohm


Observe installation position and minimum distances according to installation instructions:

Top/bottom 50mm distance

Lateral distance 20mm


Read more
Downloadcenter
Shop
Contact