High-precision universal measuring device
J.52.34.002

UMG 96-S2-CH RS485 Modbus Messgerät

Slave Gerät mit RS485, Modbus RTU

Product description

The new UMG 96-S2 energy measurement device is characterized by its universal application. It is suitable for measuring and monitoring electrical parameters and energy consumption as well as for monitoring power quality parameters such as harmonics. Applications can be found in energy distribution systems, for example for cost center recording and limit value monitoring. The device can also be used as a measurement value transmitter for building management systems or a PLC.


Main features:

-Suitable for TN and TT networks with 1 and 5 A transformer connection

-Active energy with accuracy class 0.5S (... / 5 A transformer)

-Simple tariff switching as an additional module for energy and cost transparency

-Simple integration into higher-level systems

-Open communication path via Modbus RTU

-Uncomplicated use with little configuration effort

-High performance in a compact 96 mm design with low installation depth

-Extensive options for data processing

- Multifunction measuring device with easy-to-read LCD display


General features

-Measuring accuracy for voltage, current: 0.2 %

-Measuring accuracy for active energy (kWh,... / 5 A): Class 0.5S


Inputs and outputs

-Digital output: 1

-Pulse output


RMS value measurement - Instantaneous values, e.g:

-Current, voltage, frequency

-Active, reactive and apparent power

-Power factor


Acquisition of average values, e.g:

-Voltage, current / current and maximum

-Active, reactive and apparent power / current and maximum

-Frequency / current and maximum


Measurement of power quality

-Harmonics per order/current and voltage: 1-15.

-Distortion factor THD-U / THD-I in %


Interface / protocol

-RS485 / Modbus RTU


Ambient conditions

-Temperature range, operation: K55 (-10... +55 °C)


Measuring current input (3 each)

-Rated current: 1 / 5A

-Overvoltage category: 300 V CAT II

-Sampling frequency: 8 kHz


Energy measurement

-Active, reactive and apparent energy

-Tariff switching


Measuring voltage input (4 each)

-Overvoltage category: 300 V CAT III

-Measuring range, voltage L-N, AC (without transformer): 0 ... 300 Vrms

-Measuring range, voltage L-L AC (without transformer): 0 ... 425 Vrms

-Frequency measuring range: 45 ... 65 Hz

-Sampling frequency per channel (50/60 Hz): 8 kHz

-Measurement in quadrants: 4

-Networks: TN, TT


Network visualization software

-Free GridVis Essentials


Installation:

- Connection: Voltage 3x230/400V

- 3-phase, 4-wire connection, 50/60Hz

- Current: .../5A, with galvanic isolation,

- Dimensions WxHxD: 96x9648mm

-Protection class according to EN 60529 (with seal = IP54): Front IP40 / rear IP20

-Mounting according to IEC EN 60999-1/DIN EN 50022: Front panel mounting