This range complements selected articles

Current transformer RX

Stromwandler mit Kabeldurchführung für den Schienenaufbau ab Lager lieferbar

Current transformer Disconnectable RX

Die mit einem robustem Scharnier trennbaren Wandler lassen sich einfach in bestehende Installationen einbauen. Das spart Zeit und Geld, weil keine Leiter getrennt werden müssen

Isolating current transformer KUW-1

Kabelumbau-Wandler bis 18 mm Durchmesser


Isolating current transformer KUW-2

Kabelumbau-Wandler bis 28 mm Durchmesser


Isolating current transformer KUW-4

Kabelumbau-Wandler bis 42 mm Durchmesser


Janitza current transformer

Stromwandler von Janitza - Höchste Qualität für beste Messergebnisse


M-Bus / 230V
Best price
J.52.22.069

UMG 96RM-M-CH mit 90...277 V AC, 90...250 V DC

Slave Gerät mit M-Bus Schnittstelle

Product description

The UMG 96RM with M-Bus is a very compact and powerful universal measuring device designed primarily for use in low-voltage and medium-voltage distribution systems. In addition to the large number of electrical measured values, the innovative measuring device offers a variety of additional functions, such as the measurement of harmonics up to the 40th harmonic. Continuous sampling at 21.3 or 25.6 kHz enables the measured values to be recorded in high resolution, making it an effective tool for energy management, fault analysis and power quality monitoring.


Main features:

Multifunction measuring device with easy-to-read LCD display

M-Bus interface with 2 digital outputs (as switching or pulse output)

Detailed recording of energy data and load profile

Energy management systems (ISO 50001)

High sampling rate with 21.3 kHz

Harmonics analyzer up to the 40th harmonic

Pluggable screw terminals

Backlighting

Determination of energy costs

Power quality monitoring

Measuring device with accuracy of 0.2 % (V), kWh class = 0.5S


Interfaces

M-Bus


Measurement accuracy

Work: Class 0.5 (... / 5 A)

Current: 0.2 %

Voltage: 0.2 %


Voltage quality

Harmonics up to the 40th harmonic

Rotating field components

Distortion factor THD-U / THD-I


Mains

TN, TT, IT networks

3- and 4-phase networks

Up to 4 single-phase networks


Up to 2 digital outputs

Pulse output kWh / kvarh

Switching output

Limit value output

Logic output


Installation:

Supply voltage: 90- 277V/AC (45..65Hz )

Interfaces M-Bus according to EN 13757 on terminals

Dimensions: W 96 x H 96 x D 42mm


Recommended settings for the M-Bus:

Basic configuration Optec: Readout variant 1

Code 000 / primary address (address no. 1)

 Code 001 / Baud rate (2400 baud)

 Code 080 / Measurement data (27 measurement data points)


Read more
Downloadcenter
Shop
Contact