This range complements selected articles
Stromwandler mit Kabeldurchführung für den Schienenaufbau ab Lager lieferbar
Die mit einem robustem Scharnier trennbaren Wandler lassen sich einfach in bestehende Installationen einbauen. Das spart Zeit und Geld, weil keine Leiter getrennt werden müssen
Kabelumbau-Wandler bis 18 mm Durchmesser
Kabelumbau-Wandler bis 28 mm Durchmesser
Kabelumbau-Wandler bis 42 mm Durchmesser
Stromwandler von Janitza - Höchste Qualität für beste Messergebnisse
UMG 96RM-PN-CH mit 24...90 V AC, 24...90 V DC
Product description
The UMG 96RM-PN is PROFINET-certified and suitable for use with PROFIenergy. A PROFINET certificate certifies the standard-compliant behavior according to IEC 61158 within a PROFINET network and thus ensures a high quality standard. The UMG 96RM-PN not only enables the continuous recording of consumption, but also residual current monitoring (RCM). RCM can be used to detect faults that a single system would only partially detect or not detect at all. The integrated web server can display the current power/current and voltage values in real time via the device homepage. The REST interface for querying measured values via HTTP protocol, e.g. for integrating the measurement data into higher-level software solutions (BMS, PLC, SCADA,...)
Main features:
- PROFINET-compliant Ethernet interfaces and int. switch for setting up line topologies
- Multifunction measuring device with easy-to-read LCD display
- RS485 interface with Modbus/RTU protocol
- 2 digital outputs (pulse output, switching output, limit value output, logic output)
- Optionally 3 digital inputs or outputs
- Choice of 2 RCM or temperature inputs
- Detailed recording of energy data and load profile
- Energy management systems (ISO 50001)
- High sampling rate with 21.3 kHz
- Harmonic analyzer up to the 40th harmonic
- Pluggable screw terminals
- Backlighting
- Determination of energy costs
- Power quality monitoring
- Meter with accuracy of 0.2 % (V), kWh class = 0.5S
- Energy meter with 8 tariffs, active and reactive energy
Communication:
- PROFINET
- PROFIenergy
- TCP/IP
- Modbus/TCP
- Modbus/RTU (RS485)
- HTTP/REST
Interfaces:
- RS485
- Ethernet
- PROFINET
Measuring accuracy:
- Active energy: Class 0.5S (kWh, .../5 A)
- Current: 0.2 %
- Voltage: 0.2 %
Voltage quality:
- Harmonics up to the 40th harmonic
- Rotary field components
- Distortion factor THD-U / THD-I
Networks:
- TN, TT, IT networks
- 3- and 4-phase networks
- Up to 4 single-phase networks
Temperature measurement input:
- PT100, PT1000, KTY83, KTY84
2 digital outputs:
- Pulse output kWh / kvarh
- Switching output
- Limit value output
- Logic output
- Remote via Modbus / Profibus
3 digital inputs / outputs:
- Choice of inputs or outputs
2 analog inputs:
- Analog, temperature or residual current input (RCM)
Grid visualization software:
- Free GridVis Essentials
Installation:
-Supply voltage: 24-90 V AC/24-90 V DC
-Current transformer: .../5A with 3 and/or 4-wire measurement in the neutral conductor
-Dimensions: W 96 x H 96 x D 74mm