Product description
The UMG 96RM-PN is PROFINET-certified and suitable for use with PROFIenergy. A PROFINET certificate certifies the standard-compliant behavior according to IEC 61158 within a PROFINET network and thus ensures a high quality standard. The UMG 96RM-PN not only enables the continuous recording of consumption, but also residual current monitoring (RCM). RCM can be used to detect faults that a single system would only partially detect or not detect at all. The integrated web server can display the current power/current and voltage values in real time via the device homepage. The REST interface for querying measured values via HTTP protocol, e.g. for integrating the measurement data into higher-level software solutions (BMS, PLC, SCADA,...)
Main features:
- PROFINET-compliant Ethernet interfaces and int. switch for setting up line topologies
- Multifunction measuring device with easy-to-read LCD display
- RS485 interface with Modbus/RTU protocol
- 2 digital outputs (pulse output, switching output, limit value output, logic output)
- Optionally 3 digital inputs or outputs
- Choice of 2 RCM or temperature inputs
- Detailed recording of energy data and load profile
- Energy management systems (ISO 50001)
- High sampling rate with 21.3 kHz
- Harmonic analyzer up to the 40th harmonic
- Pluggable screw terminals
- Backlighting
- Determination of energy costs
- Power quality monitoring
- Meter with accuracy of 0.2 % (V), kWh class = 0.5S
- Energy meter with 8 tariffs, active and reactive energy
Communication:
- PROFINET
- PROFIenergy
- TCP/IP
- Modbus/TCP
- Modbus/RTU (RS485)
- HTTP/REST
Interfaces:
- RS485
- Ethernet
- PROFINET
Measuring accuracy:
- Active energy: Class 0.5S (kWh, .../5 A)
- Current: 0.2 %
- Voltage: 0.2 %
Voltage quality:
- Harmonics up to the 40th harmonic
- Rotary field components
- Distortion factor THD-U / THD-I
Networks:
- TN, TT, IT networks
- 3- and 4-phase networks
- Up to 4 single-phase networks
Temperature measurement input:
- PT100, PT1000, KTY83, KTY84
2 digital outputs:
- Pulse output kWh / kvarh
- Switching output
- Limit value output
- Logic output
- Remote via Modbus / Profibus
3 digital inputs / outputs:
- Choice of inputs or outputs
2 analog inputs:
- Analog, temperature or residual current input (RCM)
Grid visualization software:
- Free GridVis Essentials
Installation:
-Supply voltage: 90- 277V/AC (45..65Hz)
-Current transformer: .../5A with 3 and/or 4-wire measurement in the neutral conductor