Separable current transformers
Optec

Separable current transformers

User-friendly and compact
  • Simple and cost-effective installation
  • Practical interlocking system: no need to disconnect
  • and disconnecting the primary conductors is no longer necessary
  • Available in various dimensions
  • No interruption to operation
  • Suitable for all measuring devices with 5 A connection
Main features Applications
  • Norms/Standard: IEC/EN 60044-1, BS 3938
  • Accuracy classes: 0.5 % or 1 %
  • Housing: 10 % glass-filled polycarbonate
  • Flame retardant according to UL standard 94V-0
  • 2 secondary connections on each side
  • M4 screws with self-locking
  • Insulation class: E (120° C maximum)
  • System voltage: 720 V maximum
  • Test voltage: 4 kV at 50 Hz - 1 min.
  • Frequency range: 50 to 60 Hz
  • Primary current ratings: 50 A to 3000 A
  • Secondary current ratings: .../5 A
  • Operating temperature: -20°C to +45° C
  • Storage temperature: -50°C to +80° C
  • Short-term current load: 60 x I TH
  • Long-term current load: 2.5 x I TH

Cost-effective Folding transformer for the installation of a subsequent transformer measurement


Measurement of high primary currents, the transformer has a small secondary current Current output, which can then be connected to measuring devices, e.g. UMG 96.


If the If the measuring device needs to be replaced, the load does not need to be switched off switched off, as the measuring device is not directly connected to the supply line in the supply line. This prevents unplanned system downtimes.


Important: Operation of the current transformer in the upper third of the specified current.

Hole opening 22 x 32mm

Article no.
Type
Primary current A
Secondary current A
Power VA
Class
RX.90-30-100
100 A
5 A
1.50 VA
Class 1
RX.90-30-150
150 A
5 A
1.75 VA
Class 1
RX.90-30-200
200 A
5 A
2.50 VA
Class 1
RX.90-30-250
250 A
5 A
3.75 VA
Class 1
RX.90-30-300
300 A
5 A
2.50 VA
Class 0.5
RX.90-30-400
400 A
5 A
3.75 VA
Class 0.5

Hole opening 82 x 52mm

Article no.
Type
Primary current A
Secondary current A
Power VA
Class
RX.125-50-250
250 A
5 A
1.00 VA
Class 0.5
RX.125-50-300
300 A
5 A
2.50 VA
Class 0.5
RX.125-50-400
400 A
5 A
2.50 VA
Class 0.5
RX.125-50-500
500 A
5 A
3.75 VA
Class 0.5
RX.125-50-600
600 A
5 A
5.00 VA
Class 0.5
RX.125-50-750
750 A
5 A
7.50 VA
Class 0.5
RX.125-50-800
800 A
5 A
7.50 VA
Class 0.5
RX.125-50-1000
1000 A
5 A
10.00 VA
Class 0.5
Article no.
Type
Primary current A
Secondary current A
Power VA
Class

Hole opening 82 x 122mm

Article no.
Type
Primary current A
Secondary current A
Power VA
Class
RX.155-80-1000
1000 A
5 A
10.00 VA
Class 0.5
RX.155-80-1200
1200 A
5 A
15.00 VA
Class 0.5
RX.155-80-1500
1500 A
5 A
20.00 VA
Class 0.5
Downloadcenter
Shop
Contact