B.91080202

EDS440-L-4 Isolationsfehlersuchgerät mit LED Display für

Gleich-, Wechsel- und Drehstromversorgungen (IT-Systemen)

Product description

The ISOSCAN EDS44x insulation fault locators are used in conjunction with the ISOMETER® iso685-D-P or the locating current injector PGH to locate insulation faults in unearthed power supplies (IT systems).

For this purpose, they use measuring current transformers to record the locating current signals generated by the iso685-D-P or IRDH575 insulation monitoring device or the PGH locating current generator and evaluate them accordingly. Up to 12 measuring current transformers can be connected to one EDS44x. A total of up to 21 insulation fault locators can be connected via an RS-485 interface (BS bus protocol), allowing up to 252 outgoing circuits to be monitored.


Main features:

- Automated insulation fault location during operation

- Main circuit application

- 12 measuring channels for measuring current transformers

- Transformer connection monitoring

- Universal system concept


Features and functions:

- Universal system concept

- Modular design, therefore easy to adapt to existing conditions

- Measuring current transformers available in various sizes and designs

- Transformer connection monitoring

- 12 measuring channels for measuring current transformer series W..., WR..., WS..

- Fault memory behavior selectable

- Setting options enable individual adjustments

- Up to 21 EDS insulation fault locators in the system, 252 measuring channels

- Response sensitivity 2...10 mA

- AC residual current measurement with adjustable response value

- Two alarm relays with one NO contact each

- Working/quiescent current selectable

- External test/reset button via digital inputs

- Display via iso685-D-P or LED display

- Central display of faulty outlets

- RS-485 serial interface, BS bus address range 2...90

- Connection to higher-level control and visualization systems possible


Technical features:

- Connection type: plug-in screw or spring terminal

- Rated insulation voltage: (IEC 60664-1) AC 250 V

- Supply voltage range Us: AC/DC 24...240 V

- Response value insulation fault location (IΔL) EDS440 2...10 mA

- Digital inputs: 2

- Digital current output: 1

- Buzzer: 1

- Interface/protocol: RS-485/BS

- Switching elements: 2 NO contacts

- Data rate: 9600 baud/s

- Dimensions (W x H x D): 72 x 93 x 63 mm


Applications:

- Insulation fault location in AC, 3AC and DC IT systems

- Main and control circuits in industrial plants and ships

- Diode-decoupled DC IT systems in power plants

- Networks for rooms used for medical purposes


Read more
Downloadcenter
Shop
Contact