LINETRAXX VMD461
Product description
The VMD461 multifunctional voltage monitoring relay monitors frequencies, undervoltages and overvoltages in DC, AC and 3(N)AC systems. The phase and/or phase-to-phase voltages are measured as an effective value and permanently shown on the device display. The measured value leading to the switching of the alarm relays is stored.
The VMD461 is equipped with additional measuring functions for:
- ROCOF df/dt
- Vector step monitoring
- Unbalance monitoring
- rotating field monitoring
equipped. The corresponding ANSI codes are stored for all available measuring functions.
Special system-related characteristics (e.g. device-specific start-up phases) can be taken into account by means of adjustable delay times. The VMD461 requires a separate supply voltage.
The optional use of the CD440 coupling device extends the monitorable voltage range to DC/3AC 1200 V or 1AC/3NAC 690 V.
Main features:
- Voltage monitoring up to 1200 V
- Display of all functions in ANSI codes
- 3-stage voltage and frequency monitoring with response and release delay
- Can be used in a wide variety of network types such as AC, 3AC, 3NAC and DC
Features and functions:
- In conjunction with the CD440 coupling device, DC networks up to 1200 V, 1AC networks up to 690 V, 3AC networks up to 1200 V and 3NAC networks up to 690 V can be monitored
- Display of all functions in ANSI codes
- Monitoring of DC, 1AC, 3(N)AC systems DIN EN 60255-1:2010-9
- Single-fault protection
- Monitoring of unbalance, phase failure, rotating field
- Monitoring of the connected (power) switches: configurable: NC/NO/off
- Islanding detection df/dt (ROCOF)
- Vector jump function
- RS-485 interface (data exchange/parameterization/software update)
- Test function for determining the switch-off time
- Test button for the tripping circuit
- Retrievability of the last 300 mains faults with time stamp/real-time clock
- Permanent monitoring of the phase and phase conductor voltage
- Separate switch-on conditions after a response value violation
- Language selection (German, English, French)
- Illuminated graphic display
- Password protection for device settings
- Remote switch-off via ripple control signal receiver
- Sealable housing
Applications:
- Monitoring of voltage-sensitive machines and systems
- Switching systems on and off above a certain voltage
- Protection of three-phase motors against phase failure and phase reversal
- Vector step detection for the protection of electrical machines
- ROCOF (rate of change of frequency) islanding detection
- Protection of transformers by detecting asymmetrical loads
Installation position:
According to the technical device manual: Any orientation