Measuring and monitoring relay
Bender

Measuring and monitoring relay

Multifunctional monitoring relays for AC/DC systems
Various measuring and monitoring relays are available for monitoring electrical and monitoring relays are available. In addition to overvoltage / undervoltage, Frequency, asymmetry, phase sequence, phase failure, loop monitoring application-specific special solutions are also possible: such as extended temperature ranges Temperature ranges, compact design, industry-specific standards or country-specific profiles.
Main features Applications

LINETRAXX VME420/421H:


  • Monitoring of undervoltage, overvoltage and frequency of AC/DC systems
  • Various monitoring functions selectable
    < U, > U, < f, > f
  • Start-up, response and release delay
  • Adjustable switching hysteresis
  • RMS value measurement (AC + DC)
  • Digital measured value display via multifunctional LC display
  • Preset function (automatic basic parameterization)
  • LEDs for operation, alarm 1, alarm 2
  • Measured value memory for trigger value
  • Permanent self-monitoring
  • Internal test/reset button
  • Two separate alarm relays, 1 changeover contact each
  • Quiescent/operating current and fault memory behavior selectable
  • Password protection for device settings
  • Sealable transparent cover
  • 2-module housing (36 mm)
  • Spring terminal (two terminals per connection)
  • RoHS-compliant


LINETRAXX VMD420/421/423:


  • Monitoring of undervoltage, overvoltage and frequency in 3(N)AC systems
  • Monitoring of asymmetry, phase failure, phase sequence
  • Various monitoring functions selectable
    < U, > U, < f, > f
  • Start-up, response and release delay
  • Adjustable switching hysteresis
  • Effective value measurement
  • Digital measured value display via multifunctional LC display
  • Preset function (automatic basic parameterization)
  • LEDs for operation, alarm 1, alarm 2
  • Measured value memory for trigger value
  • Permanent self-monitoring
  • Internal test/reset button
  • Two separate alarm relays, 1 changeover contact each
  • Quiescent/operating current and fault memory behavior selectable
  • Password protection for device settings
  • Sealable transparent cover
  • 2-module housing (36 mm)
  • Spring terminal (two terminals per connection)
  • RoHS-compliant


LINETRAXX VMD460:


  • Simple commissioning thanks to preset basic programs for country-specific standards and directives.
  • Single-fault safety
  • Monitoring of the connected coupling switches
  • Isolated network detection df/dt (ROCOF)
  • Vector jump
  • RS-485 interface (data exchange/parameterization/software update)
  • Test function for determining the switch-off time
  • Test button for the tripping circuit
  • Retrievability of the last 300 mains faults with time stamp/real-time clock
  • Permanent monitoring of phase and phase conductor voltage
  • Separate switch-on conditions after a threshold value violation
  • Language selection (German, English, Italian)
  • Illuminated graphic display
  • Password protection for device settings
  • Remote switch-off via ripple control signal receiver
  • Sealable housing


LINETRAXX VMD461 with CD440:


  • In conjunction with the CD440 coupling device, DC networks up to 1200 V, 1AC networks up to 690 V, 3AC networks up to 1200 V and 3NAC networks up to 690 V can be monitored
  • Display of all functions in ANSI codes
  • Monitoring of DC, 1AC, 3(N)AC systems DIN EN 60255-1:2010-9
  • Single-fault safety
  • Monitoring of unbalance, phase failure, rotating field
  • Monitoring of the connected (circuit) breakers: configurable: NC/NO/off
  • Islanding detection df/dt (ROCOF)
  • Vector jump function
  • RS-485 interface (data exchange/parameterization/software update)
  • Test function for determining the switch-off time
  • Test button for the tripping circuit
  • Retrievability of the last 300 mains faults with time stamp/real-time clock
  • Permanent monitoring of phase and phase conductor voltage
  • Separate switch-on conditions after a response value violation
  • Language selection (German, English, French)
  • Illuminated graphic display
  • Password protection for device settings
  • Remote switch-off via ripple control signal receiver
  • Sealable housing


  • Voltage and frequency Frequency monitoring of single-phase machines and systems
  • Earth fault monitoring via voltage transformers in medium-voltage networks
  • Monitoring of Battery systems
  • Switching systems on and off Systems above a certain voltage

VME420 / VME421H
Multifunctional monitoring relays for AC/DC systems

LINETRAXX VME420: multifunctional monitoring relay for undervoltage, overvoltage and frequency in AC/DC systems with separate supply voltage.

LINETRAXX VME421H: multifunctional monitoring relay for undervoltage, overvoltage and frequency in AC/DC systems without separate supply voltage.

Article no.
Type
Supply voltage AC
Supply voltage DC
Voltage monitoring
Frequency monitoring
Alarm relay
B.73010001
VME420-D-1
VME420-D-1
16...72 V
9,6...94 V
AC/DC 0...300 V
15...460 Hz
2x 1 changeover contact each
B.73010002
VME420-D-2
VME420-D-2
70...300 V
70...300 V
AC/DC 0...300 V
15...460 Hz
2x 1 changeover contact each
B.73010003
VME421H-D-1
VME421H-D-1
Internal energy storage
Internal energy storage
AC/DC 0...150 V
15...460 Hz
2x 1 changeover contact each
B.73010004
VME421H-D-2
VME421H-D-2
Internal energy storage
Internal energy storage
AC/DC 0...300 V
15...460 Hz
2x 1 changeover contact each

VMD420 / VMD 421 / VMD423
Multifunctional voltage relays for 3(N)AC systems

LINETRAXX VMD420: Multifunctional voltage relay for 3(N)AC systems, frequency/overvoltage/undervoltage, phase sequence, Phase failure, asymmetry detection

LINETRAXX VMD421: Monitoring of frequencies, undervoltages, Overvoltages and the voltage between two threshold values (window function) in 3(N)AC systems.

LINETRAXX VMD423: Three-phase voltage and frequency Voltage and frequency monitoring relay for self-generation systems according to DIN V VDE V 0126-1-1 (wind, water, solar systems)

Article no.
Type
Supply voltage AC
Supply voltage DC
Voltage monitoring
Frequency monitoring
Alarm relay
Special feature
B.73010005
VMD420-D-1
VMD420-D-1
16...72 V
9,6...94 V
3(N)AC 0...500 V / 288 V
15...460 Hz
2x 1 changeover contact each
B.73010006
VMD420-D-2
VMD420-D-2
70...300 V
70...300 V
AC/DC 0...300 V
15...460 Hz
2x 1 changeover contact each
B.73010007
VMD421H-D-3
VMD421H-D-3
Integrated energy storage
Integrated energy storage
AC 70...500 V
15...460 Hz
2x 1 changeover contact each
B.73010020
VMD423-D-1
16...72 V
9,6...94 V
3(N)AC 0...500 V
15...460 Hz
2x 1 changeover contact each
separate supply voltage
B.73010021
VMD423-D-2
70...300 V
70...300 V
3(N)AC 0...500 V
15...460 Hz
2x 1 changeover contact each
Separate supply voltage
B.73010022
VMD423H-D-3
Integrated energy storage
Integrated energy storage
3(N)AC 0...500 V
15...460 Hz
2x 1 changeover contact each
Power supply from monitored mains

VMD460-NA Mains and system protection

LINETRAXX VMD460: Disconnects the connection between the public Connection between the public grid and the energy Power generation system in the event of limit value violations.


B.93010045
LINETRAXX VMD460-NA-D-2
LINETRAXX VMD460-NA-D-2
AC/DC 100...240 V
Mains and system protection
Island network detection
Permanent monitoring
Remote shutdown

VMD461 Multifunctional monitoring relay

LINETRAXX VMD461 with CD440: The multifunctional voltage monitoring relay VMD461 monitors Frequencies, undervoltages and overvoltages in DC, AC and 3(N)AC systems.

B.93010047
LINETRAXX VMD461-D-2
LINETRAXX VMD461-D-2
In conjunction with CD440
Voltage monitoring up to 1200 V
3-stage voltage/frequency monitoring
Mains forms AC, 3AC, 3NAC and DC possible
B.73010046
CD440 Coupling device
CD440 Coupling device
In conjunction with VMD461

Coupling devices

Overview of AGHs for increasing the voltage range
B.914013
AGH204S-4 Coupling device
AGH204S-4 Coupling device
Rated voltage range up to AC, 3(N)AC 0...1650 V / 0...1300 V
With power converter to 1300 V
Without power converter to 1650V
B.73010046
CD440 Coupling device
CD440 Coupling device
Nominal voltage 1AC 690 V
Rated voltage 3AC 1200 V
Nominal voltage 3NAC 690 V
B.98018006
Coupling device AGH150W-4
Coupling device AGH150W-4
For AC up to 1150 V, DC up to 1760 V
Downloadcenter
Shop
Contact