Klinik Belair - Expansion and modernization of the day clinic & emergency ward

The Belair Clinic is a modern private clinic with a with a family atmosphere. It is situated in a quiet location in the residential district of Breite in Schaffhausen. The Belair Clinic belongs to the Swiss Medical Network leading private clinic group in Switzerland.


The day clinic and emergency ward were renovated as part of a modernization and expansion project. The Belair 2022 clinic was faced with this challenge. A detailed on-site analysis and corresponding risk assessment quickly revealed that the electrical power supply also needed to be renovated in accordance with the current standard requirements.


The current standard NIN 2020 Chapter 7.10 points out that the safety of patients and medical staff is the top priority in all medical areas. A safe and reliable power supply is therefore essential. As a brief power interruption and/or failure can jeopardize the treatment, diagnosis or therapy of the patient's health.

Our solution

In collaboration with the specialist planning department, a concept for the day clinic/emergency ward with 4 bunks/beds was developed. Due to the planned treatments for future patients, it was essential to realize a group 2 Room* had to be realized.

An IT network was set up for each bunk in the medical area was set up for each bunk. For this purpose, a central alarm and signaling system CP907 alarm and control unit was used for this purpose.


With the following Solution was used to implement the above requirements:

  • 4 x Automatic changeover device with integrated insulation monitoring
  • 4 x Bypass switch for maintenance purposes of the changeover devices
  • 4 x medical isolating transformers
  • 4x MK2430 operating and signaling unit Alarm signaling per bunk
  • 1x CP907 touch control panel positioned at the central station workstation with the Alarm signaling and visualization of all IT networks of the bunks and monitoring of the medical gases.

* Group 2 medically used area
- intracardiac procedures or
- vital treatment where an interruption (fault) in the power supply Power supply can cause danger to life can cause
danger to life.

What is the benefit for our customer?

The Belair Clinic has thanks to this complete solution, the Belair Clinic has a standardized and safe Power supply.


With the CP907 operating and signaling unit, the system status of the area used for medical area is constantly monitored and enables timely action to be taken.


We were on hand with our Expertise and were able to make a significant contribution to the successful a successful project completion.